Overview
This topic describes how to access the HART field instrument and its data.
Preliminary Tasks
Before you can access the HART field instrument and its data, you first need to complete the following preliminary tasks:
create a project in Control Expert
add a HART gateway module (BMEAHI0812(H) or BMEAHO0412(C)) to the project
add a HART gateway module DTM to the project
assign an IP address to the HART gateway module
enable FTP and TFTP for the CPU and the project (see referenced steps 7, 8 and 9)
add the HART field instrument DTM to the project
build the project file, connect to the CPU, then transfer the project to the CPU
Using an Animation Table to Connect to the HART Device
If the following output variables are selected in the page of the HART gateway module DTM, you may need to use an animation table to manually edit their settings:
: if the channel for a HART field instrument is not enabled, you need to enable that channel.
: if the HART field instrument detected on the HART channel is different from the instrument previously specified for that channel, you need to accept the instrument actually detected on the channel.
To manually enable a channel for a HART field instrument, and accept the instrument detected on that channel, follow these steps:
Step |
Action |
|---|---|
1 |
In the , navigate to and click the right mouse button. |
2 |
Select . A dialog of the same name opens. |
3 |
In the dialog, accept the default or type in a new name, then click . The new animation table opens. |
4 |
In the new animation table, double-click in the first cell of the first row. An ellipsis (...) appears. |
5 |
Click on the ellipsis to open an dialog. |
6 |
In the dialog, select the instance of the HART gateway module (for example a BMEAHI0812(H) module) and click . The selected object appears in the first row of the animation table. |
7 |
In the animation table, expand the nodes for the module and outputs. NOTE: If CH-Enable
and CH-ResetChanged are selected in the page, the and objects are displayed.
|
8 |
Check the HART gateway module Analog and HART channel LEDs for the HART field instrument. |
9 |
To enable every HART gateway module channel, for the object :
The channels for the HART gateway module are enabled. |
10 |
Again, check the HART gateway module Analog and HART channel LEDs for the HART field instrument. If the HART channel LED for the field instrument is flickering red, that field instrument is not recognized by the HART gateway module. |
11 |
If you need to accept the field instruments detected by the HART gateway module on every channel, for the object :
The field instruments detected by the HART gateway module are accepted. |
Accessing HART Field Instrument Data
Follow these steps to connect to a field instrument and access its data. This procedure uses the example of the KIROHNE TT51 HART field instrument.
Step |
Action |
|---|---|
1 |
In the , navigate to and right click on the HART field instrument, which is located beneath a HART gateway module. A context menu opens. |
2 |
Select to establish a connection between Control Expert and the field instrument. NOTE: When a connection is established, the HART field instrument
is displayed in bold text.
|
3 |
If necessary, select to disconnect Control Expert from the PLC. |
4 |
In the , right click on the HART field instrument. A context menu opens. |
5 |
Select to load data from the HART field instrument into Control Expert. |
6 |
In the , right click on the HART field instrument. A context menu opens. |
7 |
Select (in this example) to load data from the HART field instrument into Control Expert. |
8 |
Select the HART field instrument in the , then right click and select in the context menu. Basic HART data for the selected HART field instrument is now available from the DTM user interface. |