LED Diagnostics

Use the combined states of the RUN, ERR, I/O, BS, An and Hn LEDs to diagnose the channel and module status for the BMEAHI0812(H) and BMEAHO0412(C) modules:

LED

Description

RUN

ERR

I/O

BS

A0...An

H0...Hn

OFF

OFF

OFF

OFF

All OFF

All OFF

Module has no power, or has stopped operating.

BLK green

BLK red

BLK red

BLK red & green

All OFF

All OFF

Module is performing self-test on power-up.

OFF

BLK red

OFF

X

All OFF

All OFF

The module is not yet configured, or is in the process of configuring its channels.

ON green

BLK red

X1

X

X

X

No communication between the output module and the head module.

NOTE: The module retains the previous I/O status.

ON green

OFF

OFF

X

ON green

X

Analog channel is operational.

ON green

OFF

OFF

X

OFF

X

Analog channel is disabled.

ON green

ON red

OFF

X

OFF

X

Analog to digital conversion detected error, or power supply detected error on channel.

ON green

OFF

ON red

X

FLK

X

Overflow or underflow error detected on channel.

ON green

OFF

ON red

X

BLK

X

Broken wired detected on input sensor channel or output actuator channel.

ON green

OFF

ON red

X

OFF

X

Calibration error detected on output channel.

ON green

OFF

ON red

X

X

ON red

No response from HART device on channel.

ON green

OFF

OFF

X

X

BS red

A HART device has been detected with a major difference from the device that is configured for the channel.

ON green

OFF

OFF

X

X

FLK red

A HART device has been detected with a minor difference from the device that is configured for the channel.

ON green

OFF

OFF

X

X

ON green

A HART device has been detected that is the same as the device configured for the channel, or a device with a detected major or minor difference has been accepted.

ON green

OFF

OFF

X

X

BLK green

The HART channel is connecting to a device.

ON green

OFF

OFF

X

X

OFF

HART communication disabled for the channel.

BLK green

OFF

OFF

BLK green

X

X

The I/O module is downloading firmware.

X

X

X

OFF

X

X

The module has not been assigned an IP address.

X

X

X

BLK green

X

X

The module has no established EIP Forward Open connections, but has an IP address.

X

X

X

ON green

X

X

The module has established an Ethernet connection.

X

X

X

BLK red

X

X

The module Ethernet connection has timed out. This is cleared only when the timed out connection is re-established or if the module is reset.

OFF

X

X

ON red

X

X

The module has detected that its IP address is already in use.

ON

LED is steady on.

OFF

LED is off.

FLK

Flickering: ON for 50 ms, OFF for 50 ms, repeat.

BLK

Blinking: ON for 200 ms, OFF for 200 ms, repeat.

BS

Blinking Sequence: ON for 200 ms, OFF for 1,200 ms, repeat.

X

This LED is not used in determining the channel or module status.