Configuring Channel Properties
Use the dialog to configure the HART channels. In this dialog, you can:
enable or disable each of the HART channels
for each enabled channel specify:
the minimum number of preambles the module uses to communicate with a HART instrument
the value assigned to the primary variable if communication between the module and the HART instrument is disrupted
Create the module configuration settings offline, and then download them – along with the rest of the project configuration settings.
Configuring Parameters
You can configure the following parameters for the HART analog I/O module:
Parameter Name |
Description |
|---|---|
CH-Enable |
The state of the HART channels. The value equals the sum of the binary values of every channel that is enabled. NOTE: The parameters can be enabled or disabled in this dialog
only if is de-selected in the dialog.
|
|
Sets the status of the selected channel to one of the following settings:
|
Channel 0...(N-1) Settings |
|
|
The minimum number of preambles the HART module uses to communicate with a HART instrument. If the HART instrument requires:
Default = 5. |
|
If the HART instrument on this channel is disconnected, or if there is no HART instrument, this setting determines the value that is assigned to the primary variable ():
Default = NaN |
Restore Default Values
You can click the button to reset the modified values in this dialog to their default values.
Downloading Configuration Settings
To download an edited parameter configuration, follow these steps:
Step |
Action |
|---|---|
1 |
In the , right click on the HART gateway DTM. |
2 |
In the context menu, select . |
3 |
When the transfer is complete, the message “Transfer to FDR Server is Successful” displays. Click . |