Introduction

This topic describes the operating states for M580 standalone and Hot Standby controllers.

Operating States for Standalone Controllers

All standalone M580 PACs have these operating states:

Operating State

Description

AUTOTEST

The controller is executing its internal self-tests.

NOTE: If extended backplanes are connected to the main local backplane and line terminators are not inserted into the unused connectors on the backplane extender module, the controller remains in AUTOTEST after the self-tests have completed.

NOCONF

The application program is not valid.

STOP

The controller has a valid application, but it is stopped. The controller sets itself to predefined STOP state parameters, and can be restarted later.

HALT

The controller has an application, but it has stopped operating due to an error resulting in a blocking condition, which puts the controller in a HALT state, resulting in a recoverable or nonrecoverable condition.

RUN

The controller is executing the application program.

WAIT

The controller is in a transitory state while it backs up data when a power down condition is detected.

The controller starts again only when power is restored and the supply reserve is replenished. As it is a transitory state, it may not be viewed.

The controller performs a warm restart to exit the WAIT state.

ERROR

The controller is stopped because a hardware or system error is detected.

When the system is ready to be restarted, the controller performs a cold start to exit the ERROR state.

OS DOWNLOAD

A controller firmware download is in progress.

Monitoring the Controller Operating State

The LEDs on the controller front panel provide indications of its operating state.