The following table describes the HART DDT input objects supported by the BME AHI 0812 analog input module and the BME AHO 0412 analog output module.

Symbol

Size

Type

Access

Description

G_ModuleStatus

32 bits

DWORD

Read

Module status

G_ChannelStatus

8 bytes

DWORD

Read

Channel status1

G_ChannelStatus2

8 bytes

DWORD

Read

Channel status2

P_ChannelN_InstrumentStatus3

32 bits

DWORD

Read/Write

Channel N instrument status

P_ChannelN_PV3

32 bits

Float

Read

Channel N primary variable

P_ChannelN_SV3

32 bits

Float

Read/Write

Channel N secondary variable

P_ChannelN_TV3

32 bits

Float

Read/Write

Channel N tertiary variable

P_ChannelN_QV3

32 bits

Float

Read/Write

Channel N quarternary variable

P_ChannelN_CurrentValue3

32 bits

Float

Read/Write

Channel N current value

P_ChannelN_PercentValue3

32 bits

Float

Read/Write

Channel N percent value

P_ChannelN_UpdateCounter3

32 bits

DWORD

Read/Write

Channel N update counter

1. G_ChannelStatus contains cumulative channel status data for channels 0...3 for the:

  • BME AHI 0812 analog input module

  • BME AHO 0412 analog output module

2. G_ChannelStatus2 contains cumulative channel status data for channels 4...7 on the BME AHI 0812 analog input module.

3. N represents the channel number, as follows:

  • from 0...7 for the BME AHI 0812 analog input module

  • from 0...3 for the BME AHO 0412 analog output module

HART DDT Output Objects

The following table describes the HART DDT output objects supported by the BME AHI 0812 analog input module and the BME AHO 0412 analog output module.

Symbol

Size

Type

Access

Description

G_ResetChanged_ID

8 bits

Byte

Read

Reset changed

G_Enable_ID

8 bits

Byte

Read/Write

Channel enable