Overview

The engineering link mode lets you restrict the connection to M580 controllers to certain protocols to help secure communications with Control Expert, Control Expert Classic, and HMI panels/software. It is available for M580 controllers with firmware version 4.20 and subsequent supporting versions.

M580 Controller Connection Settings

The engineering link mode that is selected in the Security tab defines the protocols and modes to access the control project in online mode as described in the following table.

Secure engineering link(1)

Engineering link(1)

HMI/SCADA(2)

Protocols

HTTPS or HTTPS via USB

Modbus TCP or Modbus TCP via USB

Modbus TCP

Connection mode

Monitoring and programming modes

Programming mode

Monitoring mode

Engineering Link Mode

Full Access

Yes

Yes

Yes

Yes

Filtered

Yes

No

Yes

Yes

Enforced

Yes

No

No

No

(1) Connection with Control Expert or Control Expert Classic.

(2) Connection with HMI panels/software.

NOTE: For more information on drivers/protocols, refer to the topic describing the types of connections with controllers
NOTE: For more information on the programming and monitoring modes, refer to Services in Online Mode.