Introduction
The BMENOR2200H module supports Modbus TCP server and client features. In advanced mode, this service is disabled by default. (It can be enabled via web if the module is in Advanced mode.) In standard mode, this server is enabled always.The Modbus TCP server provides diagnostic data in the module's local register. The Modbus TCP Client can access this database via the module's IP address (unit ID 100).
NOTE: For details about diagnostic information for Modbus TCP, refer to the appendix of Modbus diagnostic
codes.
You can also use the module service to transfer a Control Expert configuration file to the controller over X Bus. In this case, you do not have to connect an external engineering station directly to the controller.