- Single-bit binary input point type object groups:
Group number
Used for
1
Reporting the present value of a single-bit binary input
2
Reporting single-bit binary input events or flag bit changes
- Double-bit binary input point type object groups:
Group number
Used for
3
Reporting present state value
4
Reporting double-bit binary input events or flag bit changes
- Binary output point type object groups:
Group number
Used for
10
Reporting the present output status
11
Reporting changes to the output status or flag bits
12
Issuing control commands
- Counter point type object groups:
Group number
Used for
20
Reporting the count value
21
Reporting the frozen count value or changed flag bits
22
Reporting counter events
23
Reporting frozen counter events
- Analog input point type object groups:
Group number
Used for
30
Reporting the present value
32
Reporting analog input events or changes to the flag bits
34
Reading and writing analog deadband values
- Analog output point type object groups:
Group number
Used for
40
Reporting the present value of analog outputs
41
Controlling analog output values
42
Reporting changes to the analog output or flag bits
- Time and data object groups:
Group number
Used for
50
Set or get the current time
- Class object groups:
Group number
Used for
60
Read request to specify that the outstation return some or all objects having a specified class event attribute.
- Octet string point type object groups:
Group number
Used for
110
To convey the present value
- Security statistics point type object groups:
Group number
Used for
121
Reporting the current value of the statistics
122
Reporting changes to the statistics