Overview
Communication and operation reports are part of the management parameters.
Examine the first cycle after a cold or warm start, refer to EcoStruxure™ Control Expert, System Bits and Words, Reference Manual (Related Documents).
Communication Report
This report is common to every explicit messaging function. It is significant when the value of the activity bit switches from 1 to 0. The reports with a value between 16#01 and 16#FE concern errors detected by the processor that executed the function.
The different values of this report are indicated in the following table:
Value |
Communication report (least significant byte) |
|---|---|
16#00 |
Correct exchange |
16#01 |
Exchange stop on timeout |
16#02 |
Exchange stop on user request ( |
16#03 |
Incorrect address format |
16#04 |
Incorrect destination address |
16#05 |
Incorrect management parameter format |
16#06 |
Incorrect specific parameters |
16#07 |
Error detected in sending to the destination |
16#08 |
Reserved |
16#09 |
Insufficient receive buffer size |
16#0A |
Insufficient send buffer size |
16#0B |
No system resources: the number of simultaneous communication EFs exceeds the maximum that can be managed by the processor |
16#0C |
Incorrect exchange number |
16#0D |
No telegram received |
16#0E |
Incorrect length |
16#0F |
Telegram service not configured |
16#10 |
Network module missing |
16#11 |
Request missing |
16#12 |
Application server already active |
16#13 |
UNI-TE V2 transaction number incorrect |
16#FF |
Message refused |
Operation Report
This report byte is specific to each function, and specifies the result of the operation on the remote application:
Value |
Operation report (most significant byte) |
|---|---|
16#05 |
Length mismatch (CIP) |
16#07 |
Bad IP address |
16#08 |
Application error |
16#09 |
Network is down |
16#0A |
Connection reset by peer |
16#0C |
Communication function not active |
16#0D |
|
16#0F |
No route to remote host |
16#13 |
Connection refused |
16#15 |
|
16#16 |
Remote address not allowed |
16#18 |
|
16#19 |
Connection timed out |
16#22 |
Modbus TCP: invalid response |
16#23 |
Modbus TCP: invalid device ID response |
16#30 |
|
16#80...16#87: Forward_Open response detected errors: |
|
16#80 |
Internal detected error |
16#81 |
Configuration detected error: the length of the explicit message, or the RPI rate, needs to be adjusted |
16#82 |
Device detected error: target device does not support this service |
16#83 |
Device resource detected error: no resource is available to open the connection |
16#84 |
System resource event: unable to reach the device |
16#85 |
Data sheet detected error: incorrect EDS file |
16#86 |
Invalid connection size |
16#90...16#9F: Register session response detected errors: |
|
16#90 |
Target device does not have sufficient resources |
16#98 |
Target device does not recognize message encapsulation header |
16#9F |
Unknown detected error from target |